NFPA 70E
NFPA 70E is the US standard for electrical safety in the workplace, published by the National Fire Protection Association. It covers work practices: establishing an electrically safe condition, shock and arc-flash risk assessment, approach boundaries, lockout-tagout and protective equipment. It is the companion to the National Electrical Code, which covers installation.
**NFPA 70E**, the *Standard for Electrical Safety in the Workplace*, is published by the United States National Fire Protection Association. It sets out how people should work on and around electrical equipment so as not to be injured. ## How it differs from the electrical code The NFPA is best known for **NFPA 70**, the National Electrical Code, which governs how installations are **designed and built**. NFPA 70E governs how people **work** on them. One concerns the equipment and the other the behaviour. ## Scope It applies to electrical conductors and equipment in and on buildings and other premises, including industrial sites and substations, and to the conductors connecting them to a supply. It does not cover ships, aircraft, vehicles, communications utilities or electric utilities' own generation and distribution systems, which have separate rules. ## Legal standing NFPA 70E is a voluntary consensus standard and not itself law. In practice it is treated as the **de facto standard**. The federal regulator, OSHA, sets general duties in regulation and refers to NFPA 70E as the recognised way of meeting them. Similar standards exist elsewhere, such as CSA Z462 in Canada. ## Core ideas **De-energise first.** The default expectation is that equipment is put into an *electrically safe work condition* before work begins. Working live requires justification. **An electrically safe work condition** is established by a defined sequence: identify all sources, open the disconnecting devices, verify the opening visually where possible, apply locks and tags, test each conductor for absence of voltage with an adequately rated tester that is checked before and after, and ground where necessary. See Lockout-Tagout. **Risk assessment** for two hazards: - **shock**, with approach boundaries defining how close an unqualified or qualified person may come to exposed live parts; - **Arc Flash**, with an arc-flash boundary and an estimate of incident energy in calories per square centimetre, which determines the protective clothing required. **The hierarchy of controls.** Recent editions require the assessment to apply the Hierarchy of Hazard Controls, with protective equipment as the last resort, and to consider human error. **Qualified persons.** Only those trained to recognise and avoid the hazards may do certain work. **Protective equipment** is rated by the incident energy it withstands. Ordinary clothing is not protective, whatever its fibre. ## Revisions The standard is revised on a three-year cycle. Changes relevant to proving a circuit dead: - **2018** introduced an exception allowing a permanently installed test device in place of a hand-held meter. - **2021** named it an absence of voltage tester and required listing to a product standard. - **2024** relocated the provision and stressed testing at each point of work. See Absence of Voltage Testers: What It Costs to Make a Dark Indicator Trustworthy. ## Limits The standard describes practices. It cannot make anyone follow them, and it cannot anticipate equipment that departs from a worker's expectations. Injuries continue to occur among trained people who believed they had complied; see Anatomy of an Arc-Flash Injury: A Correct Voltage Test on the Wrong Conductor.