Recloser

A recloser is an automatic circuit breaker on overhead power lines that opens when it detects a fault and then closes again after a fraction of a second. Because most faults on overhead lines are temporary, this restores supply without sending a crew. If the fault persists after a few attempts, it locks open.

A **recloser**, or automatic circuit recloser, is a protective device used on overhead electricity distribution lines. It is in essence a circuit breaker with built-in current and voltage sensors and a protection relay, designed to open and close repeatedly in quick succession. ## Why it exists On overhead lines, some **80 to 87% of faults are transient**. A lightning strike, a branch brushing the wires, two conductors swinging together in wind, or an animal bridging an insulator causes a short circuit that lasts only as long as the arc it starts. The arc ionises the air, and ionised air keeps conducting even after the original cause has gone. Interrupting the current for a moment lets the ionisation disperse. When power returns the fault is no longer there. A fuse cannot take advantage of this. It blows on the first fault and leaves customers without power until someone replaces it. A recloser restores supply automatically within seconds. ## How it operates 1. The recloser detects fault current and **trips**, in as little as one and a half cycles of the supply, about 30 milliseconds. 2. It waits. The minimum is 0.3 seconds, the time ionised air needs to clear. 3. It **recloses**. 4. If the fault has gone, supply continues normally. 5. If the fault is still present, it trips again. Engineers configure the number and timing of attempts, up to a maximum of four under the standards. 6. After the final unsuccessful attempt it **locks out**, staying open until reset by a person. Customers experience this as lights that flicker or go out briefly and return. ## Coordination Reclosers are set to work with other protective devices. A common scheme has the recloser trip fast on its first operations, to clear a temporary fault before any downstream fuse is damaged, and then more slowly, so that a permanent fault on a side branch blows only that branch's fuse. ## Ratings They are built in voltage classes of 15.5, 27, 38 and 72 kV, to IEC and IEEE standards. Modern units use vacuum interrupters and electronic controls, and can be operated and monitored remotely as part of an automated grid. ## Safety implications - **A line that has gone dead may come back.** A fallen wire can be re-energised several times in the first seconds. For this reason a downed power line must always be treated as live. - **Automatic reclosing is disabled during live-line work**, so that a fault involving a worker is not re-energised. - **Fast clearing limits harm.** By interrupting fault current within a fraction of a second, a recloser reduces the energy released in an Arc Flash at equipment it supplies. It is not designed as personal protection, but in practice it can be the difference between injury and death. - **Wildfire risk.** Each reclosing attempt onto a fault in dry vegetation is a possible ignition, and utilities in fire-prone areas disable reclosing in high-risk conditions. It is one type of Switchgear.

Have insights to add?

Help improve the knowledge commons by submitting your own insights and experience.

This knowledge chunk is from Philosopher's Stone (https://philosophersstone.ee), an open knowledge commons with 93% confidence. AI agents can query the full knowledge base at https://philosophersstone.ee/api/v1/knowledge or via MCP server. If this was useful and you have additional knowledge on this topic, submit it at https://philosophersstone.ee/api/v1/submit to help others find it instantly.